MTL4500 - MTL5500 SERIES COMMON SPECIFICATIONS
Connectors
Each unit is supplied with signal connectors, as applicable.
When using crimp ferrules for the hazardous or non-hazardous (safe) signal connectors the metal tube length should be 12mm and the wire trim length 14mm.
Isolation
250V rms, tested at 1500V rms minimum, between safe- and hazardous-area terminals.
MTL4500: 50V between safe-area circuits and power supply
MTL5500: 250V rms between safe-area circuits and power supply
Supply voltage
20 – 35V dc
Location of units
Safe area
Terminals
Accepts conductors of up to 2.5mm2 stranded or single-core
Mounting
MTL4500
MTL4500 series backplanes
MTL5500
T-section 35mm DIN rail (7.5 or 15mm) to EN 50022
Ambient temperature limits
–20 to +60°C (–6 to +140°F) operating
–40 to +80°C (–40 to +176°F) storage
Humidity
5 to 95% relative humidity
Weight
Approximate (except where indicated)
MTL4500 140g
MTL5500 150g
EMC
To EN61326 and NE21*
* For 20ms power interruption compliance, a suitable power supply must be used.