Place of Origin: | UK |
Brand Name: | MTL |
Certification: | CE |
Model Number: | MTL4546S |
Minimum Order Quantity: | 5 pcs |
---|---|
Price: | according to the purchase quantity |
Packaging Details: | carton |
Delivery Time: | approx. 4 weeks |
Payment Terms: | T/T payment |
Supply Ability: | 100pcs |
MTL4546S isolating driver for 4–20mA HART® valve positioners with line fault detection and long field lines
MTL4546S accepts a 4/20mA floating signal from a safe-area controller to drive a current/pressure converter (or any other load up to 710Ω) in a hazardous area. For HART valve positioners, the module also permits bi-directional transmission of digital communication signals. Process controllers with a readback facility can detect open circuits in the field wiring: if these occur, the current taken into the terminals drops to a preset level. The reduced maximum open-circuit voltage permits the use of longer field lines compared to MTL4546
SPECIFICATION FOR MTL4546S
See also common specification
Number of channels
One
Location of I/P converter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
Working range
4 to 20mA
Digital signal bandwidth
500Hz to 10kHz
Maximum load resistance
710Ω (14.2V at 20mA)
Minimum load resistance
90Ω
Output resistance
> 1MΩ
Under/over range capability
Under range = 1mA
Over range = 24mA (load ≤ 520Ω)
Input and output circuit ripple
< 40µA peak-to-peak
Transfer accuracy at 20°C
Better than 20µA
Temperature drift
< 1.0µA/°C
Input characteristics
Field wiring state
Normal < 6.0V
Open-circuit < 0.9mA
Short-circuit N.A.
Response time
Settles within 200µA of final value within 100ms
Communications supported
HART
Contact Person: Ms. Steven