MTL5513 (2-channel, line fault detection, phase reversal)

MTL5513 (2-channel, line fault detection, phase reversal)

MTL5513 (2-channel, line fault detection, phase reversal)

Product Details:

Place of Origin: England
Brand Name: MTL
Model Number: MTL5513

Payment & Shipping Terms:

Minimum Order Quantity: 1pc
Price: according to the purchase quantity
Packaging Details: carton
Delivery Time: in stock
Payment Terms: T/T payment
Supply Ability: 100pcs
Contact Now
Detailed Product Description

MTL5513 (2-channel, line fault detection, phase reversal)

Enables two solid-state outputs in the safe area to be controlled by two switches or proximity detectors located in the hazardous area. The Ch1/Ch2 output transistors share a common terminal and can switch +ve or -ve polarity signals. Independent output phase reversal and line fault detection are enabled via switches for each output. LFD indication is provided on the top of the module.

SPECIFICATION

See also common specification

Number of channels

Two

Location of switches

Zone 0, IIC, T6 hazardous area

Div. 1, Group A hazardous location

Location of proximity detectors

Zone 0, IIC, T4–6 hazardous area if suitably certified

Div. 1, Group A hazardous location

Hazardous-area inputs

Inputs conforming to BS EN60947–5–6:2001 standards for

Proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output characteristics

Normal phase

Outputs closed if input > 2.1mA (< 2kΩ in input circuit)

Outputs open if input < 1.2mA (> 10kΩ in input circuit)

Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD) (when selected)

User-selectable for each channel via switches on the side of the unit. Line faults are indicated by an LED for each channel. 

Open-circuit alarm on if Iin < 50µA

Open-circuit alarm off if Iin > 250µA

Short-circuit alarm on if Rin < 100Ω

Short-circuit alarm off if Rin > 360Ω

Note:  Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch

20kΩ to 25kΩ in parallel with switch

Phase reversal

Independent for each channel, user-selectable

Safe-area outputs

Floating solid-state outputs compatible with logic circuits

Operating frequency:  dc to 500Hz

Max. off-state voltage:  ± 35V

Max. off-state leakage current:  ± 50µA

Max. on-state resistance:  25Ω