MTL4614 SWITCH/ PROXIMITY DETECTOR INTERFACE

MTL4614 SWITCH/ PROXIMITY DETECTOR INTERFACE

MTL4614 SWITCH/ PROXIMITY DETECTOR INTERFACE

Product Details:

Place of Origin: UK
Brand Name: MTL
Model Number: MTL4614

Payment & Shipping Terms:

Minimum Order Quantity: 10 Pcs
Price: according to the purchase quantity
Packaging Details: carton
Delivery Time: in stock
Payment Terms: T/T payment
Supply Ability: 300 pcs
Contact Now
Detailed Product Description

MTL4614 SWITCH/ PROXIMITY DETECTOR INTERFACE 1-channel, line fault detection, phase reversal

The MTL4614 enables a load to be controlled, through a relay, by a proximity detector or switch. Line faults are signalled through a separate relay and indicated on the top of the module. Switches are provided to select phase reversal and to enable the line fault detection.

SPECIFICATION

See also common specification

Number of channels

One

Inputs

Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output characteristics

Normal phase

Outputs closed if input > 2.1mA (< 2kΩ in input circuit)

Outputs open if input < 1.2mA (> 10kΩ in input circuit)

Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD)  (when selected)

User-selectable via switches on the side of the unit. Line faults are indicated by an LED.

Line fault relay is energised and channel output relay de-energised if input line-fault detected

Open-circuit alarm on if Iin < 50µA

Open-circuit alarm off if Iin > 250µA

Short-circuit alarm on if Rin < 100Ω

Short-circuit alarm off if Rin > 360Ω

Note: Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch

20kΩ to 25kΩ in parallel with switch

Output

Channel: Single pole relay with changeover contacts

LFD: Single pole relay with changeover contacts

Note: reactive loads must be adequately suppressed

Relay characteristics

Response time:  10ms maximum

Contact rating:  10W, 0.5A, 35V dc

 

 

 

 

 

 

 

 

 

MTL4616 SWITCH/ PROXIMITY DETECTOR INTERFACE

2-channel, with line fault detection

The MTL4616 enable two loads to be controlled by a switch or proximity detector.  When selected, open or short circuit conditions in the field wiring are detected by the line-fault-detect (LFD) facility and also indicated on the top of the module. Phase reversal for each channel is selected by a switch on the side of the module and output is provided by changeover relay contacts.

SPECIFICATION

See also common specification

Number of channels

Two

Inputs

Inputs conforming to BS EN60947–5–6:2001 standards for

proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output  characteristics

Normal phase

Outputs closed if input > 2.1mA (< 2kΩ in input circuit)

Outputs open if input < 1.2mA (> 10kΩ in input circuit)

Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD)  (when selected)

User-selectable via switches on the side of the unit. Line faults are

indicated by an LED for each channel. The channel output relay is

de-energised if an input line fault is detected.

Open-circuit alarm on if Iin < 50µA

Open-circuit alarm off if Iin > 250µA

Short-circuit alarm on if Rin < 100Ω

Short-circuit alarm off if Rin > 360Ω

Note: Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch

20kΩ to 25kΩ in parallel with switch

Output

Two single-pole relays with changeover contacts

Note: reactive loads must be adequately suppressed

Relay characteristics

Response time: 10ms maximum

Contact rating: 10W, 0.5A, 35V dc

 

 

 

 

 

 

 

MTL4617 SWITCH/ PROXIMITY DETECTOR INTERFACE

2-channel, line fault detection, phase reversal

The MTL4617 enables two loads to be controlled, through a relay, by proximity detectors or switches. Line faults are signalled through a separate relay and indicated on the top of the module. Switches are provided to select phase reversal and to enable the line fault detection.

SPECIFICATION

See also common specification

Number of channels

Two

Inputs

Inputs conforming to BS EN60947–5–6:2001 standards for

proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output characteristics

Normal phase

Outputs closed if input > 2.1mA (< 2kΩ in input circuit)

Outputs open if input < 1.2mA (> 10kΩ in input circuit)

Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD)  (when selected)

User selectable by switches on the side of the module. 

Line faults are indicated by the LED for each channel.

Line fault relay is energised and channel output relay de-

energised if input line-fault detected

Open-circuit alarm on if Iin < 50µA

Open-circuit alarm off if Iin > 250µA

Short-circuit alarm on if Rin < 100Ω

Short-circuit alarm off if Rin > 360Ω

Note:  Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch

20kΩ to 25kΩ in parallel with switch

Output

Channel: Two single-pole relays with normally open contacts

LFD: Single pole relay with changeover contacts

Note: reactive loads must be adequately suppressed

Relay characteristics

Response time: 10ms maximum

Contact rating: 10W, 0.5A, 35V dc

 