Temperature Input module
These modules accept inputs from low-level dc sources such as thermocouples or RTDs in hazardous
areas and converts them into 4/20mA signals to drive safe area loads.
Early burnout detection (EBD)
When EBD is selected, the resistance of the thermocouple circuit is monitored and an alarm is
raised when there is an increase of more than 50m. This enables preventative maintenance to be
conducted on the field installation before the thermocouple actually breaks.
Configuration using PCS45/PCL45USB
Use PCS45 software, in conjunction with the PCL45USB serial link, to configure these modules. Instructions
are contained within the software.
MTL5576-RTD - Temperature Converter
Two channel, RTD/potentiometer input
The MTL5576-RTD converts signals from resistance temperature detectors (RTDs) mounted in a
hazardous area, into 4/20mA currents for driving safe-area loads. The MTL5576-RTD is compatible
with 2- and 3-wire RTD inputs.
Performance features, including input type and characterisation, ranging, monitoring, testing
and tagging are selected using PCS45 software, which is loaded onto a personal computer and
connected via the PCL45USB serial link.